Low Frequency UPS 40KVA-80KVA
HQ33 Series · Online Double Conversion · 3 Phase In / 3 Phase Out · output isolation transformer.
Capacities: 40kVA / 60kVA / 80kVA
Input
380/400/415VAC · 3 Phase + N + PE · ±25%
Output
380/400/415VAC · 3 Phase + N + PE · ±1%
Efficiency
≥93% @ 100% load
Inverter / Bypass switch
< 1 ms
| Parameter | Value |
|---|---|
| Series | HQ33 |
| Topology | Online Double Conversion |
| Power range | 40kVA / 60kVA / 80kVA |
| Working mode | 3 phase in, 3 phase out |
| Output isolation transformer | Included |
| Parallel capability | Maximum 8 units in parallel |
| Input rated voltage | 380/400/415VAC, 3 Phase + N + PE |
| Input voltage range | ±25% |
| Input rated frequency | 50/60Hz (auto-sensing) |
| Input frequency range | 45–65Hz |
| Output rated voltage | 380/400/415VAC, 3 Phase + N + PE |
| Output voltage accuracy | ±1% |
| Transient voltage response | ±5% < 10ms |
| Output power factor | 0.8 (0.9 optional) |
| Phase voltage | 220V (200–244V settable on display) |
| Crest factor | 3:1 |
| THDu | <2% @ 100% linear load; <4% @ 100% non-linear load |
| Overload (inverter) | 110%–125%: 10 min; <150%: 1 min |
| DC voltage | 384V (360–408V settable) |
| Charging current | 10–40A (settable) |
| Bypass rated voltage | 380/400/415VAC, 3 Phase + N + PE |
| Bypass voltage range | ±15% (±10% / ±20% settable on display) |
| Bypass rated frequency | 50/60Hz |
| Bypass frequency range | ±2% (±5% settable on display) |
| Inverter/Bypass switch | <1ms |
| Overload capacity (bypass) | 150%: 10 min; 175%: 1 min; 200%: 18 sec |
| Communication interface | RS232 or RS485 (MODBUS) |
| Working temperature | 0–40°C |
| Humidity | 0–95% (no condensation) |
| Altitude | <1000m no derating; >1000m derating 1% per 100m |
| Noise | ≤65 dB @ 1m |
| Minimum order | 85 |